    A single phase overhead transmission line delivers 1100 kW at 33 kV at 0.8 p.f. lagging. The total resistance and inductive reactance of the line are 10 Ω and 15 Ω respectively. Determine: i) sending end voltage ii) sending end power factor and iii) transmission efficiency.

  2. 7.

    An overhead 3-phase transmission line delivers 5000 kW at 22 kV at 0.8 p.f. lagging. The resistance and reactance of each conductor are 4 Ω and 6 Ω respectively. Determine: i) sending end voltage ii) percentage regulation and iii) transmission efficiency.