EEC 420 Power System Analysis TD 2024
À propos de ce sujet
TD 2024 de EEC420 (EEC 420) Power System Analysis (Niveau 400, Second semestre), College of Technology - COT, University of Buea : ancien sujet disponible sur Shoracy. Corrigé proposé inclus.
Ouvre ce sujet dans l'appli sur votre téléphone.
University of Buea
College of Technology - COT
Electrical / Renewable - EET/REN
Power System Analysis
TD · Second semestre · Niveau 400
Extrait du sujet
- 6.
A single phase overhead transmission line delivers 1100 kW at 33 kV at 0.8 p.f. lagging. The total resistance and inductive reactance of the line are 10 Ω and 15 Ω respectively. Determine: i) sending end voltage ii) sending end power factor and iii) transmission efficiency.
- 7.
An overhead 3-phase transmission line delivers 5000 kW at 22 kV at 0.8 p.f. lagging. The resistance and reactance of each conductor are 4 Ω and 6 Ω respectively. Determine: i) sending end voltage ii) percentage regulation and iii) transmission efficiency.
En bref
- Code du cours
- EEC420 (EEC 420)
- Type
- TD
- Année
- 2024
- Niveau
- Niveau 400
- Semestre
- Second semestre
- Corrigé proposé
- Inclus
Provenance
Université
University of BueaFaculté
College of Technology - COTDépartement
Electrical / Renewable - EET/REN